Floor slabs VPL

For the production of VPL type slabs the C40/50 grade concrete and the prestressed steel wires are used. Floor slabs comply with standard requirements and are certified.

The breadth of a standard slab is 1200 mm. Narrower slabs are also available, but the minimum breadth may not be less than 280 mm. The heights of hollow core slabs are 200 mm (VPL20), 220 mm (VPL22a), 265 mm (VPL027), and 320 mm (VPL320).

HOLLOW CORE SLABS VPL 20

SlabHeight, mmBreadth, mmExpo-sure classFire resistance classDesign load without specific weight, kPa
5678910111213141516
Max. permitted slab design length, m
VPL20-F602001200XO-XC1REI 609.408.668.37 8.037.727.44 7.196.966.76 6.576.406.24
VPL20-F60(X)2001200XC2-XA2 REI 608.047.647.296.996.736.49 6.276.085.905.745.595.45
VPL20-F902001200XO-XC1REI 908,768.448.14 7.79 7.497.226.986.766.566.38 6.216.06
VPL20-F90(X)2001200XC2-XA2REI 907.817.427.08 6.79 6.536.306.095.905.73 5.57 5.425.29

Note:
Slab weight per 1 m – 3.66 kN/m;
Slab weight per 1 m, incl. joint filling – 3.84 kN/m.

HOLLOW CORE SLABS VPL 22A

SlabHeight, mmBreadth, mmExpo-sure classFire resistance classDesign load without specific weight, kPa
5678910111213141516
Max. permitted slab design length, m
VPL22a-F602201200XO-XC1REI 609.929.559.238.958.618.318.047.687.246.856.506.19
VPL22a-F60(X)2201200XC2-XA2 REI 608.938.508.107.807.507.247.016.796.606.426.256.10
VPL22a-F902201200XO-XC1REI 909.689.339.038.738.408.107.807.336.926.556.215.91
VPL22a-F90(X)2201200XC2-XA2REI 908.708.277.927.607.327.066.836.626.436.266.105.81

Note:
Slab weight per 1 m – 3.93 kN/m;
Slab weight per 1 m, incl. joint filling – 4.13 kN/m.

HOLLOW CORE SLABS VPL 27

SlabHeight, mmBreadth, mmExpo-sure classFire resistance classDesign load without specific weight, kPa
5678910111213141516
Max. permitted slab design length, m
VPL027-F602651200XO-XC1REI 6010,209,919,659,138,487,927,437,006,626,275,965,68
VPL027-F60(X)2651200XC2-XF3REI 609,799,338,948,598,277,927,437,006,626,275,965,68
VPL027-F902651200XO-XC1REI 909,989,709,418,708,097,557,086,676,305,985,685,41
VPL027-F90(X)2651200XC2-XF3REI 909,539,088,708,368,067,557,086,676,305,985,685,41

Note:
Slab weight per 1 m – 4.27 kN/m;
Slab weight per 1 m, incl. joint filling – 4.41 kN/m.

HOLLOW CORE SLABS VPL 320

SlabHeight, mmBreadth, mmExpo-sure classFire resistance classDesign load without specific weight, kPa
5678910111213141516
Max. permitted slab design length, m
VPL320-F603201200XO-XC1REI 6012.7612.3111.9211.5811.2711.0110.339.739.198.718.277.88
VPL320-F60(X)3201200XC2-XA2REI 6011.7411.2010.7310.319.949.609.309.028.778.548.277.88
VPL320-F903201200XO-XC1REI 9012.6612.2211.8411.5111.2110.8610.189.599.068.588.167.77
VPL320-F90(X)3201200XC2-XA2REI 9011.5611.0210.5610.159.789.459.158.888.638.408.037.65

Note:
Slab weight per 1 m – 4.38 kN/m;
Slab weight per 1 m, incl. joint filling – 4.54 kN/m.

HOLLOW CORE SLABS VPL 400

SlabHeight, mmBreadth, mmExpo-sure classFire resistance classDesign load without specific weight, kPa
111213141516171820222426
Max. permitted slab design length, m
VPL400-F604001200XO-XC1REI 6012.8412.2911.6511.0710.5510.079.639.238.527.927.396.93
VPL400-F904001200XO-XC1REI 9012.6411.9411.3210.7510.249.789.358.978.287.697.186.73
VPL400-F1204001200XO-XC1REI 12012.2611.5910.9810.439.949.499.088.708.037.466.966.53
VPL400-F1804001200XO-XC1REI 18012.0811.4110.8110.279.799.348.948.577.917.356.866.43

Note:
Weight of 1 m of panel 4,98 kN/m;
Weight of 1 m of slab with joint sealing 5,39 kN/m.

EXPOSURE CLASSES

Class designationDescription of the environmentInformative examples where exposure classes may occur
No risk of corrosion or attack
XOFor concrete without reinforcement or embedded metal: all exposures, except where there is freeze/thaw, abrasion or chemical attack. For concrete with reinforcement or embedded metal: very dry.Concrete inside buildings with very low air humidity.
Corrosion induced by carbonation
XC 1Dry or permanently wet.Concrete inside buildings with low air humidity. Concrete surfaces permanently submerged in water.
XC 2Wet, rarely dry.Concrete surfaces subject to long-term water contact. Many foundations.
Chemical attack
XA 2Moderately aggressive chemical environment.Concrete exposed to chemical attack from natural soils or ground water (special studies of environmental conditions may be required).
XF 3High water saturation without de-icing agent.Horizontal concrete surfaces exposed to rain and freezing.
FIRE RESISTANCE CLASSES
REI 60 – 60 minutes
REI 90 – 90 minutes
STORAGE OF SLABS
During the storage of hollow core slabs the following requirements must be observed:

1. Only store items on a compacted ground;
2. Max. height of stacked slabs shall not exceed 2.0 m;
3. The slabs shall be separated by placing wooden beams 300-400 mm from the end of the item;
4. Wooden beams shall be placed exactly one over the other and shall not be shorter than the breadth of the slab.

More details about slabs:

Slab support locations
Stair opening installation diagrams
Lifting and storage of slabs
Filling of slab voids at the support locations
The evaluation of negative moment and additional reinforcement of slabs
VPL 20 and VPL 22a slab cutting diagrams